Description
PHOENIX TRIO-PS/1AC/24DC/ 5 2866310
Input data
| Nominal input voltage range | 100 V AC … 240 V AC |
|---|---|
| Input voltage range | 85 V AC … 264 V AC (Derating < 90 V AC: 2,5 %/V) |
| Dielectric strength maximum | 300 V AC |
| AC frequency range | 45 Hz … 65 Hz |
| Discharge current to PE | < 3.5 mA |
| Current consumption | 1.65 A (120 V AC) |
| 0.9 A (230 V AC) | |
| Nominal power consumption | 189 VA |
| Inrush current | < 15 A |
| Mains buffering time | > 20 ms (120 V AC) |
| > 110 ms (230 V AC) | |
| Input fuse | 3.15 A (slow-blow, internal) |
| Recommended breaker for input protection | 6 A … 16 A (Characteristics B, C, D, K) |
| Power factor (cos phi) | 0.72 |
| Type of protection | Transient surge protection |
| Protective circuit/component | Varistor |
Output data
| Nominal output voltage | 24 V DC ±1 % |
|---|---|
| Setting range of the output voltage (USet) | 22.5 V DC … 29.5 V DC (> 24 V DC, constant capacity restricted) |
| Nominal output current (IN) | 5 A (UOUT = 24 V DC) |
| Derating | 55 °C … 70 °C (2.5%/K) |
| Connection in parallel | Yes, for redundancy and increased capacity |
| Connection in series | yes |
| Feedback voltage resistance | 35 V DC |
| Protection against overvoltage at the output (OVP) | < 35 V DC |
| Max. capacitive load | unlimited |
| Active current limitation | Approx. 10 A (for short-circuit) |
| Control deviation | < 1 % (change in load, static 10 % … 90 %) |
| < 2 % (change in load, dynamic 10 % … 90 %) | |
| < 0.1 % (change in input voltage ±10 %) | |
| Residual ripple | < 20 mVPP |
| Output power | 120 W |
| Typical response time | < 1 s |
| Peak switching voltages nominal load | < 30 mVPP |
| Maximum power dissipation in no-load condition | 1.1 W |
| Power loss nominal load max. | 18 W |






Reviews